Maintaining Air Conditioners
Here are some very basic steps on how to maintain your air conditioning unit. This procedure can be applied to all standard window-type as well as standard split-type air conditioner units.
During summer, outside temperature reaching to near 40°C can be very irritating. Worst case if your air conditioner at home is not giving you the ample coolness the way it used to be. This problem is mostly encountered by people neglecting the proper maintenance procedure or simply neglect of doing it themselves. You have nothing to blame but yourself. But before you pick up that phone and start calling your repair man to do the maintenance for you, why not read further below and check if the recommended maintenance procedure would be beneficial and is easy to follow. Here are some very basic steps on how to maintain your air conditioning unit. This procedure can be applied to all standard window-type as well as standard split-type air conditioner units.
Precaution: Before doing any maintenance, switch off the main circuit breaker of the air conditioning unit on disconnect the air conditioning unit from the electrical outlet during maintenance.
Cleaning of air filters of split and window-type air conditioning units.
- Switch off the air conditioning unit.
- Gently pull out the air filter from the air conditioning unit.
- Clean the air filter using a vacuum cleaner.
- If the air filter is very dirty, wash it with clean water and neutral detergent (soft brush shall be used to effectively remove the dirt).
- Dry the air filter using a soft cloth / rags.
- Return the air filter to the air conditioning unit.
- Switch on the air conditioning unit if necessary.
- This procedure shall be done every 2 weeks.
Cleaning of evaporator and condenser coil of split type air conditioning units.
- Remove and recover refrigerant from the air conditioning unit using refrigerant recovery equipment. (refer to procedure 5)
- Disconnect the power supply, refrigerant lines, and drain lines from the evaporator Unit (indoor unit) and condensing unit (outdoor unit).
- Evaporator and condensing unit shall be pulled out and place in a containment pan.
- Fan impeller and casing (if any) of evaporator unit (indoor unit) and condensing Unit (outdoor unit) shall be dismantled and washed using clean water and neutral detergent or water soluble solution.
- Fan motors of indoor and outdoor unit shall be dismantled (if possible) to prevent it from being damaged during coil cleaning.
- All electrical components including fan motors of evaporator and condensing unit shall be covered with plastic or any water resistant material.
- Rinse the evaporator and condenser coil with the manufacturers approved chemical coil cleaner (approximately 2.5 to 3 liters per TR cooling capacity).
- Rinse the evaporator and condenser coil with sufficient water to remove the dirt and the chemical coil cleaner. Contaminated water collected in the containment pan should be disposed properly.
- Clean the casing (indoor and outdoor unit) and air diffuser (indoor unit only) with soft cloth or rag. Use clean water and neutral detergent if dirt and stain are difficult to remove.
- Assemble all dismantled parts of the evaporator and condensing unit.
- Drain line of indoor unit shall be flushed with the manufacturers approved liquid de-clogger (approximately 100 to 200 ml) and clean water sufficient enough to remove the clog materials. (Contaminated water from this procedure should be disposed properly.
- All refrigerants and drain line connections to the air conditioning unit shall be leak tested using nitrogen and water respectively as medium. (Soap solution shall be applied to refrigerant line connections to easily locate the leaks).
- Prior to refrigerant charging, refrigerant lines shall be subjected to flushing using nitrogen gas.
- Prepare and charge the unit with applicable refrigerant by Triple Evacuation Method.(refer to procedure 6).
- This procedure shall be done semi annually (every 6 months).
Cleaning of evaporator and condenser coil of window type air conditioning units.
- Air conditioning unit shall be pulled-out and place in a containment pan.
- Fan impellers for evaporator and condenser coil shall be dismantled and washed with clean water and neutral detergent or water soluble solution.
- All electrical components including fan motor shall be covered with plastic or any water resistant material.
- Rinse the evaporator and condenser coil with manufactures approved chemical coil cleaner (approximately 2.5 to 3 liters per TR cooling capacity).
- Rinse the evaporator and condenser coil with sufficient water to remove the dirt and chemical coil cleaner. Contaminated water collected in the containment pan shall be disposed properly.
- Clean the casing and air diffusers using a soft cloth / rag. If dirt and stains are difficult to remove, wash it with clean water and neutral detergent or water soluble solution.
- Assemble all dismantled parts of the air conditioning unit.
- Drain line of the air conditioning unit shall be flushed with manufacturers approved liquid declogger (approximately 100 to 200ml) and clean water sufficient enough to remove the clog materials. Contaminated water from this procedure shall be contained and disposed properly.
- Drain line connection shall be leak tested using water.
- This procedure shall be done quarterly (every 3 months).
Replacement of Filter Dryer
- Filter Dryer of split-type air conditioning units shall be replaced annually.
- Replacement of the said element shall be done during the cleaning of evaporator and condensing unit.
- Filter Dryer of air conditioning shall be replaced during breakdown maintenance.
- Filter Dryer connections shall be leak tested as per procedure 2.
Recovery of Refrigerant
- Prepare the refrigerant recovery equipment and one (1) empty cylinder tank of refrigerant.
- Connect the refrigerant recovery equipment to the charging port of the Condensing unit. Likewise, Refrigerant Recovery Equipment shall be connected to the empty cylinder tank of refrigerant.
- Start the Refrigerant Recovery Equipment. By-pass the lower pressure switch of the air conditioning unit by manual pressing of magnetic contactor during refrigerant recovery to prevent the compressor to stop due to low pressure refrigerant. Release the magnetic contactor when the refrigerant pressure on the gas line drops to 10 psig.
- Close the valve of the refrigerant tank and stop the Refrigerant Recovery Equipment.
Preparation of Refrigerant line and charging of Refrigerant by Triple Evacuation Method
- Connect the gauge manifold to the refrigerant lines.
- Purge all pressure from the refrigerant lines by opening the system service valves and gauge manifold hand valves.
- Connect the center hose of the gauge manifold to the vacuum pump.
- Start the vacuum pump and vacuum system of approximately -29.92 in. Hg.
- Close the gauge manifold hand valves and stop the vacuum.
- Disconnect the center hose of the gauge manifold from the vacuum pump and connect it to a cylinder containing (R-11) refrigerant.
- Open the cylinder valve.
- Loosen the center hose connection at the gauge manifold. Purge the hose for a few seconds; then tighten the connection.
- Open the gauge manifold hand valves and charge the system with (R-11) Refrigerant up to 5 psig.
- Close the refrigerant cylinder valve and gauge manifold hand valves.
- Disconnect the hose from the cylinder and purge the pressure from the system by opening the gauge manifold hand valves.
- Repeat procedures c through k for three times.
- Repeat procedure c through e.
- Disconnect the center hose of the gauge manifold from the vacuum pump and connect it to the cylinder of applicable refrigerant.
- Repeat procedure g through h.
- Open the gauge manifold hand valves and charge the system with applicable refrigerant up to the standing pressure of the cylinder tank.
- Start the air conditioning unit and add the proper charge of refrigerant
- This procedure shall be done at an ambient temperature of not less than 34°C.
-
Learn how Air Conditioners and Heat Exchangers Work
| By 5min | in Science
Learn how Air Conditioners and Heat Exchangers Work in this educational video from dizzo95....
-
Saving Money Using a Heat Pump
| By algarve | in Remodeling & Repairs
Air, earth and water have always been considered the three most important elements of our life, but in future their...
-
Fundamentals of Enthalpy Changes
| By Chand | in College and University
When a chemical reaction occurs, there is an exchange of energy between the reaction and its environment. This ex...
-
Expats leave Spain and return to the UK
| By jenny42 | in Personal Finance
Since January 2009 many British expats who thought they had made their new life in Spain have had to return to the ...
-
Feeds the dog skill
| By johnbaoo | in Dogs
Raises the dog exchange experience,Shares with the friend...
-
Self Leveling Concrete as a Floor Resurfacer | By MeetMrConcrete | in DIY
Self leveling concrete is a recent concrete technology that allows you to refinish a floor that has become flawed f...
-
Understanding the Density of Concrete | By MeetMrConcrete | in DIY
The density of concrete is a measurement of concrete's solidity. The process of mixing concrete can be modified to...
-
How To Make Roman Blinds | By barbiecrafts | in DIY
If you want to immediately change the look of your room, window treatments are an inexpensive, quick solution. And ...
-
How to obtain the best pole shed plans! | By skypilot69 | in DIY
An easy way to get plans for building a pole shed....
-
How to Fix Steam Cleaner Formula Mixer and Sprayer | By Romian1 | in DIY
You've purchased a steam cleaner or two and sooner or later the formula mixer or sprayer doesn't work. The cleaning...
-
Developing a Strong Family | By JoelEsteban | in General
This article deals with the importance of a strong family and how to achieve it....
-
Feel the Heat in Running (Part 1) | By JoelEsteban | in General
Running is the oldest and the most celebrated sporting event since the time of Greeks....
-
Calling for New Filipino Heroes | By JoelEsteban | in Human Interest
Love of country is not shown just by words but by deeds....
-
Feel the Heat in Running (Part 2) | By JoelEsteban | in General
Although it was discussed in the first part of this article, the next skill that must be learned in running, jumpi...
-
Think Green | By JoelEsteban | in Environment
Our planet is beautiful and very rich with natural resources. It is our responsibility to help make it clean and pr...








HVAC systems must be properly sized and maintained regularly to realize desired efficiency and comfort results. For example, according to US Dept of Energy website up to 30% energy savings can result from compressor energy alone if coils are cleaned vs. not. In addition this may help with dust control, promote equipment longevity, and improved indoor air quality and comfort. Most manufacturers and US Dept of Energy suggest that you inspect and clean coils and other components as much as annually. To learn more you can visit:
http://www.nadca.com
http://www.safetyking.com
http://www.ductpro.com
http://www.ductcleanersnetwork.org
http://www.energy.gov
MJ Palazzolo
President
Safety King Inc
An Energy Star Service Partner